Walk-in cooler running constantly? Why the compressor won’t shut off

Your walk-in should cool down to its set temperature and then rest. When the condensing unit runs nonstop, the box temperature drifts up and down, or frost keeps building on the pipe coming out of the cooling coil, something is out of balance. Sometimes the cause is simple, like a door that isn't sealing. Other times it's a small part most owners never see: the valve that feeds refrigerant into the coil.

What the valve at the coil does

The cooling coil inside your walk-in is called the evaporator. It's the unit near the ceiling with the fans. Liquid refrigerant flows into that coil, boils as it soaks up heat from the air, and leaves as a cold gas headed back to the compressor.

The part that controls how much refrigerant goes in is the expansion valve. It works with a small sensing bulb strapped to the pipe leaving the coil, called the suction line. The bulb tells the valve how warm the gas is when it leaves.

Techs call that reading superheat. In plain terms, it's how much the gas has warmed up after the last of the liquid boiled away. A small, steady superheat means nearly the whole coil is doing useful cooling and no liquid is escaping out the far end. When superheat rises, the valve opens a bit more. When it falls, the valve closes down. Think of it like someone filling a sink while watching the drain: enough to keep it full, never so much that it spills.

Illustrative graphic comparing three ways an expansion valve can feed a walk-in's evaporator coil. Fed right: most of the coil is cooling, superheat at the bulb is in the target range and the box can reach set temperature. Starved: ice, dirt or a restriction limits the feed, only part of the coil cools, superheat runs high and the box can run long and stay warm. Flooding or hunting: the valve is held open or swinging, liquid spills past the bulb, frost can form on the suction line, liquid can reach the compressor and box temperature can swing.
Illustrative graphic, not to scale.

Three ways the feed goes wrong

Starving: too little refrigerant. Only part of the coil gets liquid, so only part of it cools. Superheat climbs, and the system loses cooling capacity. A box in this state can run for long stretches and still struggle to hold temperature. Common causes include:

  • Moisture freezing in the valve. Refrigerant first turns really cold at the valve, so any water mixed in can freeze right there and choke the flow. This can happen even if nobody has opened the system in years. A filter-drier that's already full of water can give some back if the liquid line runs hotter than normal, for example from a slow leak, a dirty condenser coil or a failed condenser fan.
  • Dirt in the valve. Scale, metal bits or broken-down oil can work past the strainer and partly block the valve opening.
  • Bubbles in the liquid line. A restriction or a poorly sized line can let gas bubbles form before the valve, and a valve fed bubbles can't deliver its full amount.
  • Low pressure ahead of the valve. For example, when the outdoor unit runs too cold in winter. Our post on why a walk-in runs warm when it's cold outside covers that.
  • A loose or badly placed bulb. If the bulb isn't strapped firmly to a clean, straight run of pipe where it belongs, the valve gets a bad reading.

Flooding: too much refrigerant. Liquid makes it all the way through the coil and past the bulb into the suction line. Superheat drops to near zero. Liquid that reaches the compressor can damage it, which is one more reason to find the real cause when a compressor fails. Dirt or ice can hold a valve partly open, and a valve that's set too open or is too big for the job can overfeed. When that suction line runs colder than it should, frost can creep farther along it than usual.

Hunting: a feed that swings. Instead of holding steady, the valve overfeeds, then underfeeds, then overfeeds again. That swinging can cut the system's total capacity and make pressures in the coil rise and fall, and a hard swing can let liquid slip back toward the compressor. Oversized valves and coils that aren't evenly loaded with air make it worse.

Why airflow matters so much

The valve can only respond to what the coil is doing. If air can't move through the coil, the coil can't pick up heat, and the valve's feed goes off. Dirt, ice on the coil, missing panels and product stacked in the wrong place all cut airflow. When some parts of a coil get more air than others, the lightly loaded parts can let liquid through and throw off the bulb while the rest of the coil goes short.

Warning signs

  • The condensing unit runs nonstop, or nearly so.
  • The box temperature drifts up and down more than it used to.
  • Frost or ice keeps building on the pipe coming out of the coil.
  • The problem started after a repair, a leak or a change in weather.

What you can safely check

None of these need tools or involve opening the equipment.

  1. The door. Make sure it closes and latches on its own, and that nothing is propping it open during deliveries or prep.
  2. The door gaskets. Look for tears, flattened spots or gaps along the seal.
  3. The coil. From the floor, look at the unit near the ceiling. Is it iced over or heavily frosted? Don't chip at the ice. See our post on why a walk-in freezer keeps icing up.
  4. Product and airflow. Are boxes stacked against the coil or blocking the fans? Leave room for air to move in and out.

Leave valves, settings and refrigerant alone. Valve adjustments are made in small steps while measuring superheat, and changing one without gauges can create a new problem.

When to call

Call if the unit still runs nonstop after those checks, frost keeps spreading on the suction line, or product is at risk. A technician can measure superheat at the bulb, check for moisture, dirt or a restriction, confirm the bulb is mounted right and look at airflow across the coil.

We repair walk-in coolers and freezers and commercial refrigeration systems for businesses, servicing a 60-mile radius of Knoxville, TN, and we're EPA 608 Certified. Our office hours are Monday to Friday, 7 AM to 5 PM Eastern. Emergency service is available after hours. Learn more about our walk-in cooler and freezer repair and commercial refrigeration services. If your walk-in is running warm, see what to check when a walk-in cooler isn't cooling.

FAQs

Is it normal for a walk-in compressor to run all the time?

Not usually. A healthy system brings the box down to its set temperature and then cycles off. If it never gets there, something is adding load, like a door that won't seal, or holding back cooling, like a coil that's iced or underfed.

Why is there frost on the pipe coming out of my walk-in's coil?

It can mean the coil is being overfed and liquid is getting into the suction line. It isn't proof on its own, so have a technician check the superheat before anything gets adjusted.

Can I adjust the expansion valve myself?

No. Valves usually leave the factory set for typical use, and an adjustment should only be made after a technician measures the superheat and confirms one is needed.

Source: Sporlan (Parker) Form 10-143, "12 Solutions for Fixing Common TEV Problems," from the Parker Sporlan educational literature library: https://discover.parker.com/literature-educational. Also: Sporlan (Parker) Bulletin 10-9, "Thermostatic Expansion Valves: Theory of Operation, Application, and Selection," and Form 5-220, "Quick Tips," from the same library.

JW HVACR LLC

HVACR Contractor in the Knoxville, TN area.