Why is my walk-in cooler running warm when it’s cold outside?

It sounds backwards. The weather turns cold, and the walk-in that held temperature all summer starts creeping up. If your cooler or walk-in has its condenser outside, the cold itself can be the cause. When outdoor air gets cold enough, the system's pressure can drop too low to feed the cooling coil inside the box. Head pressure control is there to stop that from happening. When it's missing, set wrong or not working, the box can run warm.

What "head pressure" means, in plain English

Your refrigeration system moves heat out of the box and dumps it outside. The condenser is the outdoor unit with the fans and the finned coil. It's where that heat goes into the outside air.

Head pressure is the pressure on the hot side of the system, where the condenser is. That pressure does an important job. It pushes liquid refrigerant through a small metering valve and into the cooling coil inside your walk-in. Think of it like water pressure behind a garden hose nozzle. With good pressure, you get a full, steady spray. With weak pressure, you get a dribble.

Why outdoor condensers struggle in winter

On a warm day, the outdoor air is hot. The condenser has to work to shed heat, and head pressure stays up where it belongs.

On a cold day, the opposite happens. Cold air pulls heat out of the condenser easily, so head pressure falls. Up to a point that's fine. It can even save energy, since the compressor doesn't push as hard.

The trouble starts when head pressure drops below the minimum the system needs. Then:

  • The coil inside the box gets starved. There isn't enough push to move the refrigerant the coil needs. Part of the coil stops doing useful cooling, so the air coming off it is warmer and the box runs warm.
  • Oil can get stuck where it doesn't belong. A starved coil can trap compressor oil out in the system. The compressor's oil safety may shut it down, and oil that comes back all at once can damage the compressor.
  • The compressor runs hotter. The gas coming back to it is warmer than it should be, so the compressor works less efficiently and runs hotter.

What head pressure control does

Head pressure control keeps the condenser's pressure from falling below a set minimum when it's cold out. The system then has enough push to feed the coil, even in cold weather.

There are a few common ways to do it:

  • Fan cycling. A control turns some or all of the condenser fans off when pressure drops, so the condenser sheds less heat. It's simple, but pressure can swing up and down as the fans cycle. On a cold, windy day, wind blowing through the condenser can keep pressure low even with the fans off.
  • Condenser flooding. Valves back liquid refrigerant up inside the condenser, so less of the coil is working, and a second valve keeps the pressure up in the storage tank (the receiver). This tends to hold the steadiest pressure in cold weather. The catch is that it needs extra refrigerant and a receiver big enough to hold it in summer.
  • Splitting the condenser. Some systems split the condenser in half and shut one off in cold weather. That cuts down the extra refrigerant flooding needs.

Which method fits depends on the equipment and how it was set up. The settings matter too. Each control has to be set correctly, and if a system combines methods, they have to be set to work together.

Illustrative graphic comparing three cases for a walk-in with an outdoor condenser. On a warm day, head pressure is normal and the whole coil cools. On a cold day without head pressure control, pressure falls below the minimum, the coil is partly starved and the box can run warm. On a cold day with head pressure control, pressure is held at a set minimum and the box holds temperature.
Illustrative graphic, not to scale.

Warning signs to watch for

  • The box temperature creeps up on cold days or cold nights.
  • The problem seems to follow the weather. It's worse on the coldest days and better when it warms up.
  • The compressor shuts off on a safety, especially an oil safety, during cold weather.

Any one of these is worth a call, especially if you're holding product you can't afford to lose. If the box runs warm no matter the weather, see our post on what to check when a walk-in cooler isn't cooling.

What you can safely check yourself

You don't need tools for these, and none of them involve opening the equipment.

  1. Write down what you see. Note the box temperature, the time and roughly how cold it is outside. A few readings over a day or two help a technician find the cause faster.
  2. Check the door. Make sure the walk-in door closes all the way and the gasket isn't torn. A door that's propped open or not sealing will make any box run warm.
  3. Look at the outdoor unit from the ground or a safe spot. Is it blocked by snow, ice, leaves or anything stacked against it? Don't climb onto a roof to look.
  4. Leave the controls alone. Don't change settings on the outdoor unit, don't turn valves, and don't add refrigerant. That's work for a certified technician. Adjusting one control without checking the others can make things worse.

When to call

Call if the box won't hold temperature, if the compressor keeps shutting off, or if product is at risk. If it acted up last winter, it's worth having it checked before the next cold snap.

We work on walk-in coolers and freezers, and on outdoor condensers, for businesses, servicing a 60-mile radius of Knoxville, TN, and we're EPA 608 Certified. Our office hours are Monday to Friday, 7 AM to 5 PM Eastern. Emergency service is available after hours. Learn more about our walk-in cooler and freezer repair, commercial refrigeration installation and cold storage refrigeration for food processors.

FAQs

Why would cold weather make a cooler run warm?

An outdoor condenser sheds heat more easily in cold air, so the system's pressure drops. Below a certain point there isn't enough pressure to feed the cooling coil inside the box, and the box warms up.

Does every walk-in with an outdoor condenser need head pressure control?

Systems that run in cold weather with the condenser outside generally need some way to hold a minimum pressure. What kind, and how it's set, depends on the equipment. A technician can tell you what yours has.

Is low head pressure bad for the compressor?

It can be. A starved coil can trap oil out in the system, which can trip the compressor's oil safety or damage it when the oil returns. The compressor can also run hotter than it should.

Can I fix this by adjusting the settings myself?

No. Head pressure controls, valves and refrigerant charge work together, and changing one without gauges and training can cause new problems. Write down what you're seeing and call.

Why does my cooler run fine in summer but not in winter?

The condenser behaves very differently in hot and cold weather. A system without working head pressure control may do fine all summer, then struggle once outdoor temperatures drop.

Need help with a walk-in that's running warm? Call (865) 214-7334.

Source: Sporlan (Parker) Form 90-198, "Understanding The Fundamentals Of Head Pressure Control," from the Parker Sporlan educational literature library: https://discover.parker.com/literature-educational

JW HVACR LLC

HVACR Contractor in the Knoxville, TN area.

Previous
Previous

New compressor failed again? Why a walk-in cooler compressor keeps failing

Next
Next

Walk-In Freezer Iced Up: Why the Evaporator Keeps Freezing and What It Costs You